ATG 6000 Burn down transformer
ATG 6000 is used for the impedance reduction of cable faults in low and medium-voltage networks. This converts high-resistive, difficult to locate and intermittent faults to low-resistive faults that are easy to locate with the Time Domain Reflectometry method.
Manufacturer: BAUR (Austria).
Description
The short-circuit proof 5750 VA stray field transformer delivers a maximum voltage of DC 15 kV and is contained in a fully enclosed 19” housing. The output voltage can be changed over 8 levels that one can switch to even under load. This allows the output voltage to be adjusted to the respective cable faults. In addition, current and voltage can be limited independently of each other on each level by using potentiometers.
An external ohmmeter that can be connected to the ATG 6000 allows you to determine the fault resistance after a burn process and to evaluate whether additional burning is required.
Features
- Burning voltage up to DC 15 kV
- Output current up to 90 Arms
- Maximum input power 5750 VA
- Optimum adjustment of the output voltage over 8 voltage levels
- Voltage levels can be switched under full load
- Automatic switch-off on temperature rise
- Acoustic alarm on temperature rise
- Automatic discharge unit
- Switch-on interlock for high voltage
- Safety control unit according to DIN EN 50191
- Connection socket for external emergency stop unit with signal lamps
- Connection option for external ohmmeter
- As a stand-alone version or built-in module in BAUR cable fault location systems
|
Output voltage DC
|
max. 15 kV
|
|
Output current AC
|
90 Arms at AC 60 V
23 Arms at AC 230 V
11 Arms at AC 500 V
3.5 Arms at AC 1500 V
2.0 Arms at AC 2600 V
|
|
Output current DC
|
1.0 A at DC 5000 V
0.65 A at DC 8500 V
0.35 A at DC 15000 V
|
|
Load capacity
|
max. 14 μF
|
|
Internal discharging resistance
|
15 kOhm
|
|
Power supply
|
200 – 260 V, 50/60 Hz
100 – 130 V, 50/60 Hz (optional with external autotransformer)
|
|
Max. power consumption
|
5750 VA (in short-circuit)
|
|
Ambient temperature (operational)
|
-20 to +55 °C
|
|
Storage temperature
|
-30 to +70 °C
|
|
Dimensions (W x H x D)
|
519 x 656 x 400 mm
|
|
Weight
|
approx. 92 kg
|
Standard accessories:
- ATG 6000
- HV connection cable, 4 m, fix mounted
- Mains supply cord, 5 m
- Earth cable, 4 m, with earthing clamp
- User manual
Optional accessories:
- 19” rack, height 14 RU (622 mm), depth 400 mm, for accommodation of ATG 6000 (without carrying handles)
- Carrying handles (1 pair) for 19” rack, depth 400 mm
- Set of 4 wheels for 19” rack, mounted
- Discharge and earth rod GDR 40-250
- Remote emergency stop unit with signal lamps, incl. connection cable, 25 m
- Remote emergency stop unit with signal lamps, incl. connection cable, 50 m
- Auto transformer external, 110/230 V; 6.0 kVA