IRG 4000 time domain reflectometer |
|
|
Pulse voltage |
TDR 20 – 200 V |
|
Pulse width |
20 ns – 1.3 ms |
|
Voltage-proof up to |
400 V, 50/60 Hz |
|
Output impedance |
8 – 2,000 Ohm |
|
Input signal gain |
Dynamic range 107 dB (-63 to +44 dB) |
|
Display range |
10 m – 1,000 km (at v/2 = 80 m/μs) |
|
Accuracy |
0.1% relating to the measurement result |
|
Data rate |
400 MHz |
|
Resolution |
0.1 m (at v/2 = 80 m/μs) |
|
Velocity of propagation (v/2) |
20 – 150 m/μs, adjustable |
|
Measurement modes |
Automatic measurement mode |
|
Storage capacity |
> 100,000 measurements (hard disk limit) |
|
Display |
TFT monitor acc. to offer |
|
User interface languages |
user interface available in 22 languages |
|
Data export format |
|
|
GIS interface (option): |
Export/import GIS data |
|
Data synchronisation |
USB |
|
BAUR GeoBase Map (option) |
Full version |
|
Insulation resistance measurement |
|
|
Voltage |
up to 1,000 V |
|
Measurement range |
0 ohm – 5 Gohm |
|
Surge voltage generator |
|
|
Surge voltage ranges |
0 – 8 kV, 0 – 16 kV, 0 – 32 kV |
|
Surge energy SSG 1100 |
1,100 J (with option SZ 1550: 1,400 J, with option SZ 2650: 2,470 J) |
|
Surge sequence |
10 or 20 pulses/min, single surge |
|
DC voltage |
0 – 32 kV |
|
Max. output current (in DC mode) |
560 mA (0 – 8 kV) |