Coil command circuits |
|
|
Number of circuits |
2, 4 or 6 |
|
Type of driver |
electronic; it ensures superior timing control |
|
Driver characteristic |
300 V DC max; 60 A DC max; 300 V AC max; 42 A AC max |
|
Operating time accuracy |
0.025% of delay ± 20 us |
|
Coil current ranges |
3; 10; 60 A full scale, user selectable |
|
Coil current measurement accuracy |
0.1% of the reading ± 0.1% of the selected range |
|
Timing contact inputs (main / pir or auxiliary) |
|
|
Number of contact inputs |
16 (optionally 24), divided in 8 (optionally 12) groups of two each |
|
PIR resistance range |
30 Ω to 10 kΩ |
|
PIR resistance measurement value (optional) accuracy |
± 2% of the reading ± 0.1% of the range |
|
Contact test voltage |
24 V |
|
test current |
100 mA |
|
Auxiliary contacts |
|
|
Contact test voltage |
24 V |
|
Test current |
5 mA |
|
Voltage threshold |
15 V / 77 V or programmable with steps of 5 V |
|
Impedance |
150 kΩ or > 500 kΩ |
|
Auxiliary binary output |
|
|
Number |
One relay auxiliary output |
|
Characteristics of the contacts with a resistive load |
AC: 300 V; 8 A; 2400 VA |
|
Analog inputs |
|
|
Number of analog inputs |
8, fully programmable |
|
Measurement resolution |
16 bit |
|
Number of ranges |
3 (300 Vac (420 Vdc peak), 10 Vdc, 1 V DC) |
|
Measurement accuracy: |
|
|
Input impedance |
more than 600 kΩ |
|
Measurement sampling rate |
100 kHz max |
|
Number of insulated and independent neutrals |
4 |
|
Digital transducer inputs |
|
|
Maximum input frequency |
50 kHz |
|
Interface |
RS422 |
|
Accepted transducers |
up to 5000 impulses |
|
Micro-ohmmeters and current generator |
|
|
Output current |
200 A, 150 A, 100 A , 50 A, 25 A |
|
Resistance measurement ranges |
250 μΩ, 1 mΩ, 10 mΩ, 50 mΩ, 500 mΩ |
|
Minimum resolution |
0.1 μΩ |
|
Contact resistance accuracy |
0.2% of the reading ± 0.2% of the range (for ranges 250μΩ and 1mΩ) |
|
Maximum test voltage |
5 V |
|
Other characteristics |
|
|
Programmable sequences |
Open; Close; Open-Close; Close-Open; Open-Close-Open |
|
Display |
7” |
|
Interfaces to PC |
USB and Ethernet |
|
Memory size |
256 Mbytes (typically 1000 results) |
|
Mains supply |
from 85 to 265 V AC; 47-63 Hz |
|
Maximum supply current |
3.6 A @ 100 V AC or 1.8 A @ 200 V AC |
|
Maximum power consumption |
360 VA |
|
Dimensions |
407 x 450 x 230 mm |
|
Weight |
15 kg |
Inputs time measurement
|
Range, s |
Frequency, Hz |
Resolution, ms |
Accuracy % of the reading |
|
1 |
100 000 |
0.01 |
± 0.02 ms ± 0.01% |
|
2 |
50 000 |
0.02 |
± 0.02 ms ± 0.01% |
|
4 |
20 000 |
0.05 |
± 0.05 ms ± 0.01% |
|
10 |
10 000 |
0.1 |
± 0.1 ms ± 0.01% |
|
20 |
5 000 |
0.2 |
± 0.2 ms ± 0.01% |
|
40 |
2 000 |
0.5 |
± 0.5 ms ± 0.01% |
|
100 |
1 000 |
1 |