Coil operation |
|
|
Number of circuits |
2 (1 Open and 1 Close coils); |
|
Type of driver |
electronic; it ensures superior timing control |
|
Driver characteristic |
300 V DC max; 30 A DC max |
|
Operating time accuracy |
50 μs |
|
Measurement of the coil current |
one per channel |
|
Coil current ranges |
2.5; 10; 25 A full scale, user selectable |
|
Accuracy |
0.5% of the reading ± 0.1% of the selected range |
|
Main contact inputs |
|
|
Number of contact inputs |
6 + 6 resistor contacts (2 breaks per phase), divided in 3 groups of 2 each |
|
Resistor contact ranges |
from 20 Ohm to 10 kOhm |
|
Contact test voltage |
24 V |
|
Main contact test current |
50 mA |
|
Event inputs |
|
|
Number of auxiliary event inputs |
4, divided in 2 groups of 2 each |
|
Capability of testing dry or wet contacts |
24 V; 20 to 300 V |
|
Test current |
2 mA |
|
Sample rates |
20kHz - 10kHz - 5 kHz - 2kHz - 1kHz - 500Hz - 200Hz - 100Hz, 50 Hz and 20 Hz user selectable |
|
Timing accuracy |
50 μs ± 0.025% of the time reading at 20 kHz |
|
Maximum record length |
1000 s |
|
Analog inputs |
|
|
Number of analog inputs |
8 (10 Optional) |
|
Input voltage range |
± 5 V; ± 50 V; ± 500 V user selectable |
|
Analog input measurement resolution |
16 bit |
|
Microhmmeter - static and dynamic resistance measurement module (option) |
|
|
DC Test current |
200 A, 100 A, 25 A |
|
Contact resistance range |
200 μOhm; 1.000 mOhm; 10.00 mOhm; 100.0 mOhm; user selectable |
|
Resistance measurement accuracy (range 100 mOhm) |
± 1% of the reading ± 0.2% of the range |
|
Minimum trip voltage test (option) |
|
|
Two options |
250 V - 4 A; 70 V - 10 A |
|
Maximum voltage adjustement |
up to 50% of nominal DC Voltage |
|
Digital transducer |
|
|
Number of digital transducer |
3 |
|
Input type |
RS 422 - Single ended for incremental encoders with quadrature signal |
|
Max input frequency |
50 kHz |
|
Power supply |
5 V and 12 V |
|
Connections |
3 multiple connectors |
|
Other characteristics |
|
|
Programmable sequences |
Open; Close; Open-Close; Close-Open; Open-Close-Open |
|
Display |
large graphical high brightness sunlight display (122 x 92 mm) |
|
Interfaces to PC |
USB and RS232 |
|
Memory size |
256 Mbytes (500 results) |
|
Mains supply |
from 85 to 265 V AC; 50-60 Hz |
|
Internal battery |
NiMh |
|
Dimensions |
490(W) x 370(D) x 240(H) mm |
|
Weight |
13 kg basic unit; |