AC Current outputs |
||||
Range A AC |
Current output, A |
Max power, VA |
Load time, s |
Recovery time, min |
100 |
30 |
300 |
steady |
- |
100 |
800 |
60 |
15 |
|
250 |
1000 |
1 |
5 |
|
40 |
12 |
300 |
Steady |
- |
40 |
800 |
60 |
15 |
|
80 |
1000 |
1 |
5 |
|
10 |
5 |
400 |
Steady |
- |
10 |
800 |
60 |
15 |
|
20 |
1000 |
2 |
5 |
|
AC Voltage outputs |
||||
Range V AC |
Voltage output, V |
Max power, VA |
Load time, min |
Recovery time, min |
250 |
250 |
500 |
steady |
- |
250 |
750 |
10 |
45 |
|
DC Voltage outputs |
||||
Range V AC |
Voltage output, V |
Max power, VA |
Load time, min |
Recovery time, min |
300 |
300 |
300 |
steady |
- |
300 |
500 |
10 |
45 |
|
Current measurement |
||||
Range |
Resolution |
Accuracy |
||
From 0 to 9.999 s |
1 ms |
± (1 ms + 0.005%) |
||
From 10.0 to 99.99 s |
10 ms |
± (10 ms + 0.005%) |
||
From 100.0 to 999.9 s |
100 ms |
± (100 ms + 0.005%) |
||
From 1.000 to 9.999 s |
1 s |
± (1 s + 0.005%) |
||
Output |
Range |
Resolution |
Accuracy |
|
10 A |
1.999 A |
1 mA |
± (1% + 5 mA) |
|
19.99 A |
10 mA |
± (1% + 20 mA) |
||
40 A |
7.999 A |
4 mA |
± (1% + 20 mA) |
|
79.99 A |
40 mA |
± (1% + 80 mA) |
||
100 A |
19.99 A |
10 mA |
± (1% + 50 mA) |
|
199.9 A |
100 mA |
± (1% + 200 mA) |
||
249.9 A |
100 mA |
± (1% + 200 mA) |
||
Voltage measurement |
||||
Output |
Range |
Resolution |
Accuracy |
|
250 V AC |
1.99 V |
1 mV |
± (1% + 50 mV) |
|
19.99 V |
10 mV |
± (1% + 50 mV) |
||
199.9 V |
100 mV |
± (1% + 200 mV) |
||
299.9 V |
300 mV |
± (1% + 300 mV) |
||
300 V DC |
19.99 V |
10 mV |
± (0.5% + 50 mV) |
|
199.9 V |
100 mV |
± (0.5% + 200 mV) |
||
399.9 V |
300 mV |
± (0.5% + 300 mV) |
||
65,130 V AC |
19.99 V |
10 mV |
± (1% + 20 mV) |
|
199.9 V |
100 mV |
± (1% + 200 mV) |
||
260 V AC |
19.99 V |
10 mV |
± (1% + 20 mV) |
|
199.9 V |
100 mV |
± (1% + 200 mV) |
||
299.9 V |
300 mV |
± (1% + 300 mV) |
||
130 V DC |
19.99 V |
10 mV |
± (0.5% + 20 mV) |
|
199.9 V |
100 mV |
± (0.5% + 200 mV) |
||
260 V DC |
19.99 V |
10 mV |
± (0.5% + 20 mV) |
|
199.9 V |
100 mV |
± (0.5% + 200 mV) |
||
299.9 V |
300 mV |
± (0.5% + 300 mV) |
||
Angle and frequency measurement |
||||
Measurement |
Range |
Resolution |
Accuracy |
|
Phase |
0-360 |
1° |
1° ± 1 Digit |
|
Frequency |
15.000 - 499.999 |
1 mHz |
±(0.1% +1 mHz) |
|
External current measurement |
||||
Input |
Range |
Resolution |
Accuracy |
|
20 mA |
0.02 A DC |
0.1 mA |
± (0.5% + 0.1 mA) |
|
10 A |
1.999 A AC |
1 mA |
± (1% + 2 mA) |
|
9.99 A AC |
10 mA |
± (1% + 20 mA) |
||
1.999 A DC |
1 mA |
± (0.5% + 2 mA) |
||
9.99 A DC |
10 mA |
± (0.5% + 20 mA) |
||
External voltage measurement |
||||
Range |
Resolution |
Accuracy |
||
9.999 V AC |
2 mV |
± (1% + 10 mV) |
||
99.99 V AC |
10 mV |
± (1% + 20 mV) |
||
599.9 V AC |
100 mV |
± (1% + 200 mV) |
||
9.999 V DC |
2 mV |
± (0.5% + 10 mV) |
||
99.99 V DC |
10 mV |
± (0.5% + 20 mV) |
||
599.9 V DC |
100 mV |
± (0.5% + 200 mV) |
||
Other Characteristics |
||||
Test settings can be stored and recalled from the T 1000 PLUS local memory |
up to 10 test settings |
|||
Test results can be saved into a permanent local memory |
up to 500 test results saved |
|||
Interface |
USB |
|||
Mains supply |
230 V ± 15% 50-60 Hz or 120 V ± 15%50-60 Hz |
|||
Maximum supply current |
5 A |
|||
Dimensions |
380 (w) x 300 (d) x 240 (h) mm |
|||
Weight |
19 kg |