Logo_ESKAN.png
UA EN

eKAM Electronic primary injection test set

eKAM test system includes two portable units: one control unit with a large graphical display that adjusts the AC voltage output (up to 220 V) and one current unit (up to 2000, 3000, 5000A).
BUX 2000 (2000 A) - BUX 3000 (3000 A) - BUX 5000 (5000 A): one or more BUX current unit can be connected to eKAM (not simultaneously), they can be ordered separately when the order is placed or at a later moment.

Manufactory: ISA - ALTANOVA GROUP (Italy).

Description

eKAM includes three measurement inputs:
  • DC voltage
    • High range (300 V DC)
    • Medium range (10 V DC)
  • AC voltage:
    • High range (300 V AC)
    • Medium range (10 V AC)
    • Low range (3 V AC)
  • Current (10 A AC or DC)
All these inputs are independent among them (unless 3V and 300V) and allow the measurement of CT outputs or of another source. In addition, a digital input (up to 300 V) is available: it can measure the timing of a wet or dry contact. The instrument is housed in a transportable aluminium box, which is provided with a cover and handles for ease of transportation. A transport case can also be supplied upon request.
Features
  • Fully automatic primary injection test system
  • CT ratio, burden and polarity test
  • Circuit breaker testing
  • Two portable units: control and current units
  • High current output: up to 2000 A, 3000 A and 5000 A and AC voltage output up to 220 V
  • Variable output frequency: 15÷500 Hz
  • Large graphic display
  • Advanced Test & Data Management Software for test set control, results storage and analysis
  • Step & Touch plus ground resistance tests with STLG option, according to EN50522 and EN61936-1 standards
  • Line impedance test with STLG option
  • Reduced timing test
  • USB interface and Ethernet interface for PC connection
  • IEC 61850-9-2 sample values protocol interface
  • Compact and lightweight: Control unit: 17 kg Current unit: 16/20 kg according to the model

Generator output (max voltage output 220 V)

Output power, VA     

Max test duration, s     

Frequency, Hz

1500

Steady

15 to 500

4000

300

15 to 500

5000

25

15 to 50

Input measurements

Input

Range

Accuracy (reading & range)

AC CURRENT

1 A; 10 A

<%0.05 <%0.05

DC CURRENT

1 A; 10 A

<%0.03 <% 0.08

HIGH AC VOLTAGE

300 mV; 3 V;

<%0.15 <%0.05

30 V; 300 V

<%0.05 <%0.05

LOW AC VOLTAGE

30 mV

<%0.1 <%0.25

300 mV

<%0.08 <%0.08

3 V

<%0.03 <%0.08

DC VOLTAGE

10 mV; 100 mV

<%0.05 <%0.15

1 V; 10 V

<%0.03 <%0.08

Phase angle measurement

Range

Resolution

Accuracy

0 - 360°

0.01°

< 0.15°

Other measurement (Z, P, R, X, S, Q, cos(ϕ))

Range

Resolution

Accuracy (reading & range)

0÷9.999

1

<%0.15 <%0.15

Other characteristics

Display

TFT, 640 x 480, coloured, 132 x 99 mm, backlight

Communication interfaces     

ETHERNET for the PC connection, USB port for the USB key     

Mains Supply

100-230 V ± 15%; 50-60 Hz

Maximum supply current

16 A

Dimensions

450 (W) x 400 (H) x 230 (D) mm

Weight

17 kg

BUX Technical Specification

BUX 2000

Test current, A

Output power, VA

Test duration, s

500

700

infinite

1000

1500

60

2000

5000

25

BUX 3000

Test current, A

Output power, VA

Test duration, s

1000

900

infinite

2000

2400

300

3000

4800

60

BUX 5000

Test current, A

Output power, VA

Test duration, s

1000

700

infinite

2000

1500

300

3000

2700

30

4000

4200

20

5000

5500

10

Standard accessories:

  • eKAM
  • One mains supply cable, 2 m long
  • One grounding cable, 6 m long
  • One interface cable for the USB port
  • One ETHERNET interface cable
  • One USB pen drive
  • One cable for the 10A measurement to be connected to the secondary of the CT 2.5 sq. mm, 10 m long
  • Four crocodiles for measurements connections (two red and two black)
  • One cable for voltage measurements 1 sq. mm, 10 m long
  • Two short cables, 2m long (red and black), for other measurements
  • One adaptor for 10V input - measuring BUX cable

Optional accessories:

  • BUX 2000 (3000, 5000)
  • Transport case for eKAM
  • Transport case of BUX unit
  • Line impedance testing kit
  • Step & Touch testing kit
  • Trolley for eKAM
  • Stud (16, 20 or 25 mm) for Step & Touch testing kit
  • Remote safety switch
  • Warning strobe light
  • PADS software (primary)- Primary, CTs, VTs test module
Back to the list