Logo_ESKAN.png
UA EN

T 3000 Primary current injection test set

T 3000 is a unique solution for all testing operations during commissioning and maintenance of substations, as it allows to perform the test of over-current relays, current and voltage transformers. It is also capable of testing energy meters and transducers. In addition, T 3000 incorporates a powerful multimeter and phase angle meter, and oscilloscope functions.

Manufactory: ISA - ALTANOVA GROUP (Italy).

Description

T 3000 contains three independent generators:
  • Main generator. It has six outputs: High AC current; Low AC current; Low DC current; Current impulses; High AC voltage; Low AC voltage
  • Auxiliary AC voltage generator: it generates an independent, phase adjustable AC voltage
  • Auxiliary DC voltage generator, to feed the relay under test.
All outputs are adjustable and metered on the large, graphic LCD display. With the multi-purpose control knob and the graphic LCD display it is possible to enter the MENU mode,
that allows to control all functions, and makes T 3000 the most powerful testing device, with manual and automatic testing capabilities, and with the possibility to transfer test results to
a PC via the RS232 interface. These results can be recorded, displayed and analysed by the powerful TDMS software, which operates with all WINDOWS versions, starting from WINDOWS 98 included.
Features
  • Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers
  • Primary injection testing capabilities
  • 3000 V AC high-pot test
  • Generates up to 800 A (option: 2000 - 3000 - 4000 A)
  • Microhmmeter function (option): up to 400 A DC
  • Large graphic display
  • Test results and settings are saved in the local memory
  • RS232 interface for PC connection
  • Compact and lightweight

High AC current output
Application: CT testing (ratio, polarity, burden), primary injection, relay testing (electro-mechanical (high power) and numeric (low power))

Current output, A

Output power, VA

Load time, s

Recovery time, min

100

600

steady

-

150

8000

15 min

30

200

1000

4 min

15

400

1600

15

5

600

2000

5

3

800

2000

1

2

Low AC current output (High power range)
Application: CT testing (burden, secondary side), VT testing (overcurrent protection), Over-current relay testing

Range, A

Current output, A

Output power, VA

Max test duration, s

Recovery time, min

40

12

300

steady

-

18

 

15 min

30

24

 

4 min

15

36

800

15

5

48

 

5

3

60

1000

1

2

10

5

400

steady

-

7.5

 

15 min

30

10

800

60

15

15

 

30

10

20

1000

15

5

Low AC current output (Low power range)
Application: CT testing (burden, secondary side), VT testing (overcurrent protection), Over-current relay testing

Range, A

Current output, A

Output power, VA

Max test duration, s

Recovery time, min

40

12

60

steady

-

17

10 min

30

23

60

10

36

1

2

10

5

60

steady

-

6

10 min

45

7

60

2

10

1.5

2

Low DC current output
Application: CT testing (winding resistance, burden resistance), PT testing (tap-changer contact resistance)

Current output, A

Load resistance, Ohm

Output power, VA

Max test duration, min

6

0

0

steady

3

2

18

steady

1

8

8

steady

High AC voltage output (3000 V version)
Application: CT testing (excitation curve, voltage withstand), VT testing (ratio, polarity, electronic voltage transformer), PT testing (ratio per tap), 1A CT’s

Voltage output, V

Current output, A

Output power, VA

Max test duration, min

3000

0.2

600

steady

2500

0.6

1500

1

High AC voltage output (1200 V version)
Application: CT testing (excitation curve, voltage withstand), VT testing (ratio, polarity, electronic voltage transformer), PT testing (ratio per tap), 5A CT’s

Voltage output, V

Current output, A

Output power, VA

Max test duration, min

1200

0.5

600

steady

1200

1.5

1800

1

Low AC voltage output
Application: CT testing (ratio with voltage method, saturation curve)

Voltage output, V

Current output, A

Output power, VA

Max test duration, min

250

0.5

125

steady

220

1.15

250

3

Auxiliary AC voltage
Application: Relay testing

Range, V

Max current, mA

65

500

130

250

260

125

Auxiliary DC Voltage

Range, V

Current limit, A

Power, W

130

0.9

90

240

0.45

90

Timer

Inputs

free of voltage or with voltage

Programmable voltage threshold

24 V or 80 V

Metering range, in seconds

from 0 to 9.999 s; 10.00 to 99.99 s; 100.0 to 999.9 s; 1000 to 9999 s

Metering range, in cycles

from 0 to 1000.0 cycles; from 1000 to 500,000 cycles

Counting mode

this mode is foreseen for the test of energy meters

Maximum input frequency

10 kHz

Auxiliary binary output

Contact range

5 A; 250 V AC; 120 V DC

Measuring section

Phase angle measurement accuracy

Frequency accuracy

1 mHz

Current measurements

Two inputs: 20 mA AC or DC or 10 A AC
Accuracy: 0.5%

Voltage measurement

Two inputs: 10 V or 600 V, AC or DC
Accuracy: 0.5%

Ratio

0.1 to 9999;
Accuracy: 0.5% typical; 1% max

Resistance

Up to 250 Ohm;
Accuracy: 0.5% typical; 1% max

Other characteristics

Display

FSTN, 240x128 pixels (135x80 mm)

Local memory

up to 500 results

Interface

RS232

Mains supply

230 V ± 10%; 50-60 Hz, or
120 V ± 10%; 50-60 Hz

Dimensions

455 (W) x 325 (D) x 290 (H) mm

Weight

31 kg


Standard accessories:

  • T 3000
  • Connection cable and test connectors
  • Spare fuses (no. 5), T16A
  • Software TDMS with user manual
  • User’s manual

Optional accessories:

  • Thermal printer 112 mm
  • Aluminium transport case
  • Plastics transport case
  • High IDC Module - 400 A
  • FT 1000 current filter
  • Earth resistance and resistivity test kit
  • D 1000 differential relay test module
  • Current Clamp 1/1000 Max 100A
  • SU 3000 Safety device for the line impedance measurement
Back to the list