T 2000 Primary current injection test set

T 2000 is a unique solution for all testing operations during commissioning and maintenance of substations, as it allows to perform the test of over-current relays, current and voltage transformers. In addition, T 2000 incorporates a powerful multimeter and phase angle meter, and oscilloscope functions.

Manufactory: ISA - ALTANOVA GROUP (Italy).

Description

T 2000 includes a multiple generator, with six outputs:
  • High AC current;
  • Low AC current;
  • Low DC current;
  • Current impulses;
  • High AC voltage;
  • Low AC voltage.
The selected output is adjustable and metered on the large, graphic LCD display. With the multipurpose control knob and the graphic LCD display it is possible to enter the MENU mode, that allows to control all functions, and makes T 2000 the most powerful testing device, with manual and automatic testing capabilities, and with the possibility to transfer test results to a PC via the RS232 interface. These results can be recorded, displayed and analysed by the powerful TDMS software, which operates with all WINDOWS versions, starting from WINDOWS 98 included.

Features
  • Multi function system for testing: current, voltage and power transformers
  • Current transformer excitation, ratio and polarity test set
  • Primary injection testing capabilities
  • 3000 V AC high-pot test
  • Generates up to 800 A (option up to 4000A with high current booster)
  • Microhmmeter function (option) up to 400A DC
  • RS232 interface for pc connection
  • Test results and settings are saved into local memory
  • Compact and lightweight

High AC current output
Application: CT testing (ratio, polarity, burden), primary injection, relay testing (electro-mechanical (high power) and numeric (low power))

Current output, A

Output power, VA

Load time, s

Recovery time, min

100

600

steady

-

150

8000

15 min

30

200

1000

4 min

15

400

1600

15

5

600

2000

5

3

800

2000

1

2

Low AC current output (High power range)
Application: CT testing (burden, secondary side), VT testing (overcurrent protection), Over-current relay testing

Range, A

Current output, A

Output power, VA

Max test duration, s

Recovery time, min

40

12

300

steady

-

18

 

15 min

30

24

 

4 min

15

36

800

15

5

48

 

5

3

60

1000

1

2

10

5

400

steady

-

7.5

 

15 min

30

10

800

60

15

15

 

30

10

20

1000

15

5

Low AC current output (Low power range)
Application: CT testing (burden, secondary side), VT testing (overcurrent protection), Over-current relay testing

Range, A

Current output, A

Output power, VA

Max test duration, s

Recovery time, min

40

12

60

steady

-

17

10 min

30

23

60

10

36

1

2

10

5

60

steady

-

6

10 min

45

7

60

2

10

1.5

2

Low DC current output
Application: CT testing (winding resistance, burden resistance), PT testing (tap-changer contact resistance)

Current output, A

Load resistance, Ohm

Output power, VA

Max test duration, min

6

0

0

steady

3

2

18

steady

1

8

8

steady

High AC voltage output (3000 V version)
Application: CT testing (excitation curve, voltage withstand), VT testing (ratio, polarity, electronic voltage transformer), PT testing (ratio per tap), 1A CT’s

Voltage output, V

Current output, A

Output power, VA

Max test duration, min

3000

0.2

600

steady

2500

0.6

1500

1

High AC voltage output (1200 V version)
Application: CT testing (excitation curve, voltage withstand), VT testing (ratio, polarity, electronic voltage transformer), PT testing (ratio per tap), 5A CT’s

Voltage output, V

Current output, A

Output power, VA

Max test duration, min

1200

0.5

600

steady

1200

1.5

1800

1

Low AC voltage output
Application: CT testing (ratio with voltage method, saturation curve)

Voltage output, V

Current output, A

Output power, VA

Max test duration, min

250

0.5

125

steady

220

1.15

250

3

Timer

Inputs

free of voltage or with voltage

Programmable voltage threshold

24 V or 80 V

Metering range, in seconds

from 0 to 9.999 s; 10.00 to 99.99 s; 100.0 to 999.9 s; 1000 to 9999 s

Metering range, in cycles

from 0 to 1000.0 cycles; from 1000 to 500,000 cycles

Counting mode

this mode is foreseen for the test of energy meters

Maximum input frequency

10 kHz

Auxiliary binary output

Contact range

5 A; 250 V AC; 120 V DC

Measuring section

Phase angle measurement accuracy

Frequency accuracy

1 mHz

Current measurements

Two inputs: 20 mA AC or DC or 10 A AC
Accuracy: 0.5%

Voltage measurement

Two inputs: 10 V or 600 V, AC or DC
Accuracy: 0.5%

Ratio

0.1 to 9999;
Accuracy: 0.5% typical; 1% max

Resistance

Up to 250 Ohm;
Accuracy: 0.5% typical; 1% max

Other characteristics

Display

FSTN, 240x128 pixels (135x80 mm)

Local memory

up to 500 results

Interface

RS232

Mains supply

230 V ± 10%; 50-60 Hz, or
120 V ± 10%; 50-60 Hz

Dimensions

455 (W) x 325 (D) x 290 (H) mm

Weight

31 kg

Standard accessories:

  • T 2000
  • Set of connection cables, included in a suitable transport case with wheels and handle
  • Spare fuses (no. 5), T16A
  • Software TDMS with user manual
  • User’s manual

Optional accessories:

  • Thermal printer 112 mm
  • Aluminium transport case
  • Plastics transport case
  • Current clamp 1/1000 Max 100A
  • High IDC Module 400 A
  • FT 1000 current filter
  • Earth resistance and resistivity test kit
  • SU 3000 Safety device for the line impedance measurement