High AC voltage |
|||
|
The high AC voltage output up to 2kV is coming from a transformer that provides to insulate the outputs from the power supply. |
|||
|
Range |
Resolution |
Typical Error |
Guaranteed Error |
|
2100 V |
100 mV |
< 0,02 % < 0,02 % |
± 0,05 % ± 0,05 % |
|
Low AC current |
|||
|
The output current can be manually adjusted using the front panel controls |
|||
|
Range |
Resolution |
Typical Error |
Guaranteed Error |
|
10 A |
1 mA |
< 0,025 % < 0,025 % |
± 0,05 % ± 0,1 % |
|
Low DC current |
|||
|
Output current can be manually adjusted using the front panel controls |
|||
|
Range |
Resolution |
Typical Error |
Guaranteed Error |
|
15 A |
1 mA |
< 0,025 % < 0,025 % |
± 0,05 % ± 0,05 % |
|
Low AC voltage |
|||
|
Range |
Resolution |
Typical Error |
Guaranteed Error |
|
300 V |
15 mV |
< 0,02 % < 0,02 % |
± 0,05 % ± 0,05 % |
|
Low voltage for excitation curve DC method |
|||
|
Range |
Resolution |
Typical Error |
Guaranteed Error |
|
200 V |
10 mV |
< 0,025 % < 0,025 % |
± 0,05 % ± 0,05 % |
|
20 mV |
1 μV |
< 0,05 % < 0,05 % |
± 0,01 % ± 0,01 % |
|
Output frequency |
|||
|
Range |
Resolution |
Accuracy |
|
|
15Hz – 400Hz |
10mHz |
< 100 ppM; output voltage > 200 V |
|
|
Ratio test (accuracy for CT ratio measurements) |
|||
|
Range |
Typical accuracy |
Maximum accuracy |
|
|
0,8 ÷ 2000 |
± 0,02 % |
± 0,05 % |
|
|
Ratio test (accuracy for VT ratio measurements) |
|||
|
Range |
Typical accuracy |
Maximum accuracy |
|
|
1 ÷ 400 |
± 0,03 % |
± 0,2 % |
|
|
Phase Angle |
|||
|
Range |
Resolution |
Accuracy (cosφ 0.8 - 1) |
|
|
0° ÷ 360.0° |
0.01° (< 1 minute) |
< 4 minutes (maximum) For amplitudes more tha |
|