Logo_ESKAN.png
UA EN

TD 5000 Tan delta test set

The high-voltage generator TD 5000 is a complementary module of STS serie. TD 5000 designed to perform Tan Delta measurements, dissipation factor and capacitance of transformer and bushing at the frequency of the mains or in a wide frequency range.

Manufactory: ISA - ALTANOVA GROUP (Italy).

Description

The following table lists the tests that can be performed on power transformers and high-voltage apparatus:
  • Tan Delta (or dissipation factor DF): from 0 to more than 100%;
  • Capacitance: from 1 pF to 200 μF;
  • Power factor : from 0 to 100%
Features
  • Optional module for STS 5000 and STS 4000 test set, standard module for STS 3000 light
  • Tan Delta, capacitance, dissipation factor measurements and for exciting current test
  • Output voltage from 12 V up to 12 kV
  • Variable output frequency: 1 - 500 Hz
  • PADS - Power Apparatus Diagnostic Software for automatic testing, assessment and report
  • Compact and lightweight
  • Patented technology

Max voltage output

12 kV

Max current output

300 mA

Frequency

1…500 Hz

Capacitance

Measurement range 1

from 1 pF to 5μF. Resolution: 6 digits.
Accuracy, typical: ± 0.03% of the value ± 0.1 pF;
guaranteed: < 0.1% of the value +1pF (from 45 to 70 Hz)

Measurement range 2           

from 5 μF to 200 μF. Resolution: 6 digits.
Accuracy, tipical: ±0.1% of the value ±0.1 nF,
guaranteed: <0.5% of the value ±1 nF

Tan Delta or Dissipation Factor DF

Measurement range 1

from 0 to 10% (capacitive). Resolution: 5 digits;
accuracy, typical: 0.05% of the value ± 0.005 %;
guaranteed: 0.1% of the value ± 0.005 % (from 45 to 70 Hz, current < 10 mA)

Measurement range 2

from 0 to 100%. Resolution: 5 digits;
accuracy, typical: 0.3% of the value ± 0.01 %;
guaranteed: 0.5% of the value ± 0.02 %

Measurement range 3

over 100%. Resolution: 5 digits;
accuracy, typical: 0.5% of the value ± 0.03 %;
guaranteed: 0.8% of the value ± 0.05 %

Power Factor PF (or cos (φ))

Measurement range 1

from 0 to 10% (capacitive). Resolution: 5 digits;
accuracy, typical: 0.05% of the value ± 0.005 %;
guaranteed: 0.1% of the value ± 0.005 % (from 45 to 70 Hz, current < 10 mA)

Measurement range 2

from 0 to 100%. Resolution: 5 digits;
accuracy, typical: 0.3% of the value ± 0.02 %;
guaranteed: 0.5% of the value ± 0.02 %

Impedance

From 1kOhm to 1400 MOhm. Resolution: 6 digits
Accuracy, typical 0.3% of the value ± 0.1%,
guaranteed <0.5% of the value.

Power

Measurement ranges

10 kW, 100 kW, 1 MW

Resolution (6 digits)

0.1 mW

Accuracy

<0.5% of the value ± 1 mW

Inductance

Measurement range 1

from 1 H to 10 kH. Resolution (6 digits): 0.1 mH;
accuracy, typical: 0.3% of the value ± 0.5 mH;
guaranteed: 0.5% of the value

Measurement range 2

from 100 H to 10 MH. Resolution (6 digits): 1 H;
accuracy, typical: 0.3% of the value;
guaranteed: <0.5% of the value

Excitation Current

Range 1

10 mA. Resolution: 0.1 μA;
accuracy, typical: 0.2% of the value ± 0.1μA;
guaranteed: 0.3% of the value ± 0.1μA

Range 2

300 mA. Resolution 1 mA;
accuracy, typical: 0.2% of the value ± 1 mA;
guaranteed: 0.5% of the value ± 0.5% of the range

Output Frequency

AC output frequency range: 1 to 500 Hz

Max Interference Conditions at Line

Electrostatic

15 mA rms of the interference current into any lead or
cable with no loss of measurement accuracy

Electromagnetic

500 μT, at 50 Hz in any direction

General information

Dimensions

440 (W) x 345 (H) x 210 (D) mm

Weight

25 kg


Standard accessories:

  • TD 5000

Optional accessories:

Back to the list