Generator Output |
|||||
|
Low AC current output |
|||||
|
Maximum output current |
6 / 3 А |
||||
|
Maximum output voltage |
70 / 140 V |
||||
|
Maximum output power |
360 VA |
||||
|
Connection |
two safety 4 mm banana sockets |
||||
|
Frequency range |
15 - 500 Hz |
||||
|
Low DC current output |
|||||
|
Maximum output current |
6 A DC |
||||
|
Maximum output voltage |
65 V DC |
||||
|
Maximum output power |
360 W |
||||
|
Connection |
two safety 4 mm banana sockets |
||||
|
High AC Voltage output |
|||||
|
MAX. VOLTAGE OUTPUT V |
CURRENT OUTPUT A |
OUTPUT POWER VA |
MAX. TEST DURATION S |
||
|
2000 |
1,25 |
2500 |
60 |
||
|
1 |
2000 |
130 |
|||
|
0,5 |
1000 |
> 2 hours |
|||
|
1000 |
2,5 |
2500 |
60 |
||
|
2 |
2000 |
130 |
|||
|
1 |
1000 |
> 2 hours |
|||
|
500 |
5 |
2500 |
60 |
||
|
4 |
2000 |
130 |
|||
|
2 |
1000 |
> 2 hours |
|||
|
Measurement accuracy |
< 0.05% of the reading, < 0.05% of the range |
||||
|
Phase error |
< 0,1° |
||||
|
Output connection |
two HV safety sockets |
||||
|
Output frequency |
15 – 500 Hz |
||||
|
Current measurement of the HV output |
|||||
|
CURRENT RANGE A |
ACCURACY |
PHASE ERROR |
|||
|
5 |
< 0.2% reading < 0.05% range |
< 0,1° |
|||
|
0,5 |
< 0.05% reading < 0.05% range |
< 0,1° |
|||
|
0,05 |
< 0.1% reading < 0.1% range |
< 0,2° |
|||
|
Low AC Voltage output |
|||||
|
Voltage range |
140 / 70 V AC |
||||
|
Output power |
420 VA |
||||
|
Frequency range |
15 - 500 Hz |
||||
|
Connection |
two safety 4 mm banana sockets |
||||
|
Measuring Inputs |
|||||
|
Current and Voltage |
|||||
|
INPUT |
RANGE |
ACCURACY |
|||
|
AC CURRENT |
1 / 10 А |
± (0.05 % reading + 0.05 % range) |
|||
|
DC CURRENT |
1 / 10 А |
± (0.03 % reading + 0.08 % range) |
|||
|
HIGH AC VOLTAGE |
300 mV / 3 V |
± (0.15 % reading + 0.05 % range) |
|||
|
30 / 300 V |
± (0.05 % reading + 0.05 % range) |
||||
|
LOW AC VOLTAGE |
30 mV |
± (0.1 % reading + 0.25 % range) |
|||
|
300 mV |
± (0.08 % reading + 0.08 % range) |
||||
|
3 V |
± (0.03 % reading + 0.08 % range) |
||||
|
DC VOLTAGE |
10 / 100 mV |
± (0.05 % reading + 0.15 % range) |
|||
|
1 / 10 V |
± (0.03 % reading + 0.08 % range) |
||||
|
Binary Input - Timer |
|||||
|
Voltage thresholds |
5 V, 24 V, 48 V or > 80 V |
||||
|
Timer resolution |
1 ms |
||||
|
Phase Angle |
|||||
|
MEASUREMENT |
RANGE |
RESOLUTION |
ACCURACY |
||
|
PHASE |
0 – 360° |
0.01° |
< 0.1° |
||
|
Resistance measurement |
|||||
|
SOURCE |
RANGE |
ACCURACY |
|||
|
LOW DC CURRENT 6 А |
100 mΩ |
< 0.3 % |
|||
|
1 Ω |
< 0.3 % |
||||
|
10 Ω |
< 0.2 % |
||||
|
DC V METER |
100 Ω |
< 0.6 % |
|||
|
1 kΩ |
< 0.5 % |
||||
|
20 kΩ |
< 0.5 % |
||||
|
Other Characteristics |
|||||
|
Display |
TFT LCD- display, 640 x 480, 132 x 99 mm, с Backlight |
||||
|
Communication interfaces |
ETHERNET for the PC connection |
||||
|
Interfaces to external modules: |
Commands to TD 5000 and STCS; Alarms to a flashing light; Remote start input. |
||||
|
Mains supply |
100-230 V ± 15%; 48-62 Hz |
||||
|
Dimensions |
450 (W) x 400 (H) x 230 (D) mm |
||||
|
Weight |
22 kg |
||||