SCAR 10 Surge arrester testing

SCAR 10 is used to check regularly the efficiency of the metal oxide surge arrester in service that are installed on the high voltage transmission and distribution networks.
SCAR 10 performs the test according to the IEC standard 60099-5 A1 ED. 1.0 Section 6: Diagnostic indicators of metal-oxide surge arresters in service - Method B1 and B2.

Manufactory: ISA - ALTANOVA GROUP (Italy).

Description

On-line leakage current measurement methods
SCAR 10 allows to carry out the control while the surge arrester is in service, analyzing by means of a special current clip-on transformer the leakage current in the surge arrester ground connection. The values of this current normally range from fractions of milliampere to a few milliampere, and are characterized by a third harmonic distortion whose value is an indicator of the deterioration of the surge arrester.
The resistive component of this leakage current may increase due to different stresses causing ageing and finally causing arrester failures.

Third harmonic with compensation
In case there is a doubt that the third harmonic comes from a heavy distortion of the voltage rather than the surge arrester itself, the auxiliary measuring probe provided with the SCAR 10 allows to measure this content quite easily in order to perform the compensation. This problem does not apply to HV arresters, as on HV lines the voltage distortion is almost negligible (typically 0.2%), while the limit for the arrester is 2% up. For MV arresters, the measurement of the third harmonic content in the voltage is easily performed connecting the instrument to the secondary of a P.T. of the line under test. The environment during the measure is characterized by the presence of high electric and magnetic fields. In order to minimize their effects on the measurement, the clip-on transformer is completely screened; also, the signal pre-amplifier is located on the transformer’s handle. Thanks to this arrangement, the cable connecting the clip-on transformer to the measuring instrument is less sensitive to the electric and magnetic field.

Features
  • On-line diagnostic of metal oxide surge arresters
  • According to IEC 60099-5 A1 “Diagnostic indicators of metal-oxide surge arresters in service”
  • Third harmonic analysis of leakage current with compensation
  • Extensive field experience
  • Easy, fast and reliable diagnostic method
  • Safe lightweight equipment
  • Highest quality, safety and reliability
  • Worldwide high quality technical support in 100 countries

Clamp-on current transformer

Current ratio

1000:1

Ratio error from 0,1 mA to 10 mA

5% ± 0,05 μA

Load resistance

47 Ohm

Frequency response

less than - 0.5 dB from 50 Hz to 10000 Hz

Tightening diameter

54 mm

Jaw opening

over 55 mm

Weight

0,9 kg

Dimensions

123 х 240 х 28 mm

Measuring instruments

Range of total current rms and peak measures      

1.999 mA, for currents less than 1 mA,
or 19.99 mA for higher currents

Third harmonic range

199.9 μA for currents less than 0,1 mA,
or 1999 μA for higher currents

Response of the third harmonic filter

< - 60 dB at 50 Hz
0 dB at 150 Hz
< - 20 dB at 250 Hz and higher frequencies

Accuracy

50 Hz measure, rms and peak value: total maximum of ± 5% from 0.1 to 10 mA
150 Hz rms measure: total maximum of ± 10% from 10 to 1000 μA

Display

Liquid crystal display, with 3.5 digits

Power supply

by means of four AA alkaline penlight batteries

Battery life

over 50 hours with 10% back lighting;
25 hours with continuous back lighting

Instrument container

for hand-carrying

Weight of the instrument alone

0.75 kg

Dimensions

200 x 112 x 65 mm

Standard accessories:

  • SCAR 10
  • Токоизмерительные клещи C47-IS;
  • Набор проводов;
  • Кейс для транспортировки;
  • Токовая закоротка;
  • Руководство по эксплуатации;
  • Гарантийный талон ООО ГК «Энергоскан».

Optional accessories: