PQM-703 Power quality analyzer

PQM-703 is a technically advanced product that allows for comprehensive measurements of  the quality of electricity, analysis and recording of power network parameters, for frequencies 50/60 Hz  in accordance with European standard EN 50160.

Manufactory: SONEL S.A. (Poland).

Description

PQM-703 in relation to the PQM-702 has new functions like recording of transients  with max. sampling frequency 10 MHz  (rapid changes in voltage) and control signals. Minimal transient capturing time is 650 ns. It is intended for a very wide range of users who need to control the quality of power with a mobile device , which fulfills the requirements of a multi-sheet standard IEC 61000 for class A analyzers. This applies to measurement accuracy, measurement methods, and synchronization of time with a standard signal. The last condition is met with a built-in GPS module with an internal antenna. If  the analyzer is installed inside,  it is possible to use an additional antenna with a 10m-long wire. If the antenna is situated outside, GPS signal will be attainable without any problems and used for the synchronization of an internal clock.
Features
  • Power from the measured network
  • Designed for use in virtually all network types from 64 V to 760 V directly, with particular emphasis on measurements at low voltage poles, due to the ease of installation
  • Independent power supply makes it particularly suitable for measurements behind voltage transformers. It can also be used for measurements in DC voltage systems
  • Remote configuration and data transfer in real time using the built-in GSM modem
  • Anti-theft function – text message notification in case of position change – built-in GPS receiver
  • Real time clock synchronized using GPS protocol

Parameter

Measuring range

Max. resolution

Accuracy

Alternating voltage (TRMS)

-

0,0…1000,0 V or 0.0…760.0 V

4 significant digits

±0.1% Unom

Crest Factor

Voltage

1.00…10.00 (≤1.65 for 690 V voltage

0.01

±5%

Crest Factor

Current

1.00…10.00 (≤3.6 dla Inom)

0.01

±5%

Alternating current (TRMS)

-

depending on clamp

4 significant digits

±0.1% Inom (error does not account for clamp error)

Frequency

-

40.00...70.00 Hz

0.01 Hz

±0.01 Hz

Active, reactive, apparent and distortion power

-

depending on configuration (transducers, clamps)

4 significant digits

depending on configuration (transducers, clamps)

Active, reactive and apparent energy

-

depending on configuration (transducers, clamps)

4 significant digits

as power error

cosφ and power factor (PF)

-

-1.00...1.00

0.01

±0.03

tgφ

-

-10.00...10.00

0.01

depends on error of active and reactive power

Harmonics and interharmonics

Voltage

DC, 1...50

as for alternating voltage True RMS

±0.05% Unom for m.v. < 1% Unom
±5% m.v. for m.v. ≥ 1% Unom

Harmonics and interharmonics

Current

DC, 1...50

as for alternating current True RMS

±0.15% Inom for m.v. < 3% Inom
±5% m.v. for m.v. ≥ 3% Inom

THD

Voltage and
current

0.0..100.0% (relative to RMS value)

0.1%

±5%

Active and reactive power of harmonics

-

depending on configuration (transducers, clamps)

epends on minimum current and voltage values

-

Angle between current and voltage harmonics

-

-180.0…+180.0°

0.1°

±(n x 1°)

K-Factor

-

1.0...50.0

0.1

±10%

Flicker index

-

0.20...10.00

0.01

±5%

Unbalance factor

Voltage and current

0.0...20.0%

0.1%

±0.15% (absolute error)

Measurement of control signals

Voltage

up to 15% Unom at 5.00...3000.00 Hz

4 significant digits

unspecified for <1% Unom
±0.15% for 1...3% Unom
±5% for 3...15% Unom

Measurement of transients

Voltage

±8000 V

4 significant digits

±(5% + 25 V)


Standard accessories:

  • 3 x crocodile clip, black, 1 kV, 20 A
  • 2 x crocodile clip, red, 1 kV, 20 A
  • Crocodile clip, blue, 1 kV, 20 A
  • Crocodile clip, yellow, 1 kV, 20 A
  • AC-16 line splitter
  • AZ-1 power supply adapter (mains plug/banana inputs)
  • Voltage adapter with M4/M6 thread – set 5 pcs
  • 4 x magnetic voltage adapter – set
  • Straps for mounting on a pole – set – 1.2 m
  • DIN rail mounting bracket with positioning catches
  • 2 x fasteners and bands for mounting the analyzer
  • XL2 carrying case
  • Data transfer and analysis (USB cable, Sonel Analysis software)
  • User manual

Optional accessories:

  • F-1A flexible clamp (Φ=360 mm)
  • F-2A flexible clamp (Φ=235 mm)
  • F-3A flexible clamp (Φ=120 mm)
  • C-4A clamp (Ø 52 mm) 1000 A AC
  • C-5A clamp (Ø 39 mm) 1000 A AC/DC
  • C-6A clamp (Ø 20 mm) 10 A AC
  • C-7A clamp (Ø 24 mm) 100 A AC
  • L2 carrying case for clamps
  • Magnetic voltage adapter
  • Flat test clip (grip – banana socket) (5 pcs)
  • Test clips with steel jaws – set (5 pcs)
  • Adapter for control terminals (5 pcs)
  • AGT-16C threephase socket adapter 16 A / 32 A (PEN)
  • AGT-16P threephase socket adapter 16 A / 32 A
  • AGT-16T industrial socket adapter 16 A / 32 A
  • AGT-63P threephase socket adapter 63 A
  • PQM magnetic strap (2 pcs)
  • ASX-1 piercing adapter (4 pcs)
  • GPS antenna
  • GSM repeater
Back to the list