Measurement of interference voltage |
||
|
Range |
Resolution |
Accuracy |
|
0...100 V |
1 V |
±(2% m.v + 3 digits) |
|
Measurement of interference frequency |
||
|
Range |
Resolution |
Accuracy |
|
15...450 Hz |
1 Hz |
±(1% m.v. + 2 digits) |
|
Measurement of earthing resistance (method 3- and 4-pole) (0,100 Ω...19,9 kΩ) |
||
|
Range |
Resolution |
Accuracy |
|
0,000...3,999 Ω |
0,001 Ω |
±(2% m.v. + 4 digits) |
|
4,00...39,99 Ω |
0,01 Ω |
±(2% m.v. + 2 digits) |
|
40,0...399,9 Ω |
0,1 Ω |
|
|
400...3999 Ω |
1 Ω |
|
|
4,00k...19,99 kΩ |
0,01 kΩ |
±(5% m.v. + 4 digits) |
|
Measurement of earth connection and equipotential bonding (2P) (0,045 Ω...19,99 kΩ) |
||
|
Range |
Resolution |
Accuracy |
|
0,000...3,999 Ω |
0,001 Ω |
±(2% m.v. + 4 digits) |
|
4,00...39,99 Ω |
0,01 Ω |
±(2% m.v. + 2 digits) |
|
40,0...399,9 Ω |
0,1 Ω |
|
|
400...3999 Ω |
1 Ω |
|
|
4,00k...19,99 kΩ |
0,01 kΩ |
±(5% m.v. + 2 digits) |
|
Measurement of resistance of auxiliary electrodes Rh and Rs |
||
|
Range |
Resolution |
Accuracy |
|
0...999 Ω |
1 Ω |
±(5% (Rs +Re +Rh) + 8 digits) |
|
1,00...9,99 kΩ |
0,01 kΩ |
|
|
10,0...19,9 kΩ |
0,1 kΩ |
|
|
Measurement of multiple earthing resistance with using the clamp and auxiliary electrodes (3p + clamp) (0,120...1999 Ω) |
||
|
Range |
Resolution |
Accuracy |
|
0,000...3,999 Ω |
0,001 Ω |
±(8% w.m. + 4 digits) |
|
4,00...39,99 Ω |
0,01 Ω |
±(8% w.m. + 3 digits) |
|
40,0...399,9 Ω |
0,1 Ω |
|
|
400...1999 Ω |
1 Ω |
|
|
Measurement of multiple earthing resistance with using double clamps |
||
|
Range |
Resolution |
Accuracy |
|
0,00...19,99 Ω |
0,01 Ω |
±(10% m.v. + 3 digits) |
|
20,0...149,9 Ω |
0,1 Ω |
±(20% m.v. + 3 digits) |
|
Measurement of ground resistivity (Measurement method: Wenner, r=2pLRE) |
||
|
Range |
Resolution |
Accuracy |
|
0,0...199,9 Ω |
0,1 Ω |
depending on measurement accuracy Rе |
|
200...1999 Ω |
1 Ω |
|
|
2,0...19,99 kΩ |
0,01 kΩ |
|
|
20,0...99,9 kΩ |
0,1 kΩ |
|
|
100...999 kΩm |
1 kΩ |
|
|
Measurement of AC current (leakage) |
||
|
Range |
Resolution |
Accuracy |
|
0,1...99,9 mA |
0,1 mA |
±(8% m.v. + 5 digits) |
|
100...999 mA |
1 mA |
±(8% m.v. + 3 digits) |
|
1,00...4,99 A |
0,01 A |
±(5% m.v. + 5 digits) |
|
5,00...9,99 A |
0,01 A |
±(5% m.v. + 5 digits) |
|
10,0...99,9 A |
0,1 A |
|
|
100...300 A |
1 A |
|
|
Measurement of dynamic earthing resistance (Ro) with impulse wave method (4 ) |
||
|
Range |
Resolution |
Accuracy |
|
0,0...99,9 Ω |
0,1 Ω |
±(2,5% m.v. + 3 digits) |
|
100...199 Ω |
1 Ω |
|