Logo_ESKAN.png
UA EN

MZC-304 Loop meter

MZC-304 is dedicated to personnel performing measurements in single and multi-family buildings, office buildings, industrial plants and any other places equipped with low voltage electrical systems. In addition, the meter is intended for maintenance personnel working on objects, where fault currents reach 4.4 kA (measured according to EN 61557). MZC-304 is also a great tool for checking circuits additionally protected by residual current devices.

Manufactory: SONEL S.A. (Poland).

Features
  • Fault loop impedance measurement with 0.01 Ω resolution
  • Low-current impedance measurement in circuits protected by RCD ≥ 30mA with 0.01 Ω resolution (range of 180...270 V)
  • Operates in networks with voltages 220/380 V, 230 V/400 V, 240/415 V (operating range 180...460 V)
  • Operating voltage range: 180…270 V (for ZL-PE and ZL-N) and 180…460 V (for ZL-L)
  • Maximum measuring current: 7.6 A for 230 V (3x10 ms), 13.3 A for 400 V (3x10 ms)
  • Operating frequency 45…65 Hz
  • Calculation of Ik fault current
  • Measurement with swapped L and N conductors
  • Measurement of resistance (RS) and reactance (XS) components
  • Low-voltage measurement of continuity of circuit and resistance

Measurement functions

Measurement range

Display range

Resolution

Accuracy

Voltage

0 V…500 V

0 V…500 V

from 0.1 V

from ±(2% m.v. + 2 digits)

Frequency

45.0 Hz…65.0 Hz

45.0 Hz…65.0 Hz

0.1 Hz

±(0.1% m.v. + 1 digit)

Short-circuit loop parameters

2p method - standard current measurement
maximum current 13.3 A

from 0.13 Ω…1999 Ω
acc. to EN 61557

0.00 Ω…1999 Ω

from 0.01 Ω

±(5% m.v. + 3 digits)

2p method - measurements
without tripping RCDs

from 0.5 Ω…1999 Ω
acc. to EN 61557

0.00 Ω…1999 Ω

from 0.01 Ω

from ±(6% m.v. + 5 digits)

Short-circuit current readings

2p method - standard current measurement

Calculated on the basis of test
ZS ranges and rated voltages

1.110 A…40.0 kA

from 0.001 A   

Calculated on the basis
of error for fault loop

2p method - measurements
without tripping RCDs

Calculated on the basis of test
ZS ranges and rated voltages

1.110 A…24.0 kA

from 0.001 A

Calculated on the basis
of error for fault loop

Measurement of continuity of protective conductors and equipotential bonding

Low-voltage measurement of continuity
of circuit and resistance with ±200 mA current     

0.12 Ω…400 Ω
acc. to EN 61557-4

0,00 Ω…400 Ω

from 0.01 Ω

±(2% w.m. + 3 cyfry)

Measurement of resistance with low current

0.0 Ω…1999 Ω

0.0 Ω…1999 Ω

from 0.1 Ω

±(3% w.m. + 3 cyfry)


Standard accessories:

  • MZC-304
  • WS-05 adapter with UNI-SCHUKO angular plug
  • Pin probe 1 kV (banana socket) red / blue
  • Crocodile clip 1 kV 20 A yellow
  • Test lead 1.2 m (banana plugs) red / blue / yellow
  • M1 hanging straps
  • M6 carrying case
  • 4x LR6 1.5 V battery
  • User manual

Optional accessories:

  • WS-01 adapter with START button with UNI-Schuko plug
  • WS-07 adapter for measuring Z(L-N) loop
  • Crocodile clip 1 kV 20 A red / blue
  • Pin probe 1 kV (banana socket) yellow
  • Test lead 5 / 10 / 20 m red 1 kV (banana plugs)
  • Industrial socket adapter 16A / 32A
  • Three-phase socket adapter 16A / 32A
  • Three-phase socket adapter 16A / 32A
  • Three-phase socket adapter 63 A