MIC-5001 Insulation resistance meter
MIC-5001 with adjustable testing voltage up to 5 kV. It is a great tool for assessing the condition of electrical insulation in residential buildings, industry, railways and other facilities of general use. Due to its parameters - excellent performance, low power consumption from batteries, the option of charging them during measurements, convenience of use and a high ingress protection level - it is perfect for maintenance teams, testing motors, cables, street lighting or at the construction and maintenance of photovoltaic systems.
Manufacturer: SONEL S.A. (Poland).
Description
The meter may be used to measure the insulation resistance using the adjustable test voltage up to 5000 V. When testing the cables, it automatically discharges their load at the moment of completing the measurement.
MIC-5001 allows the user to determine the insulation resistance by applying linearly increasing voltage with the slope of 1 kV/s, according to standard EEE Std 95TM-2002. This functionality is called RampTest.
In contrast the maximum test voltage, this slow and uniform method of applying test voltage protects the insulation against sudden “electrical stress”. This process may reveal defects that cannot be observed in classic RISO resistance measurement. If the tested insulation is weakened or defective, RampTest will enable the user to determine its maximum withstand voltage. In addition, this functionality is particularly useful in testing rotating machines or surge arresters.
The meter has a built-in voltmeter of AC and DC voltages in the range of up to 750 V. Extensive memory allows the device to record and send to a computer nearly 12,000 measurement results. Download Sonel Reader software from manufacturer’s website to analyse the measurement results and present them in graphic form, e.g. current or resistance values shown in a function of time.
Features
- Measurement voltage selected within the range of 50…500 V with steps of 50 V and from 500 to 5000 V with steps of 100 V
- Continuous reading of measured insulation resistance or leakage current
- Automatic discharge of the measured object’s capacitance upon completion of insulation resistance measurement
- Sound signalling of five-second time intervals, facilitating capture of time characteristics
- Timing of measurement time T1, T2 and T3 for measurement of dielectric absorption ratio (DAR) and polarization index (PI)
- Reading of actual measurement voltage during measurement
- Protection against measurement of live objects
- Two- or three-lead method of insulation resistance measurement
- Insulation resistance measurement according to the RampTest method and breakdown voltage measurement with ramping rate up to ~1 kV/s
- Measurement of direct and alternating voltages within the range of 0...750 V
- 990-cell memory (11,880 entries), data transmission to PC via USB cable
- Power supplied by accumulator
- Instruments meet the requirements laid down by standard EN 61557
- The meter can be powered and charged from an external power adapter or from a car lighter socket
|
Insulation resistance measurement
|
|
Range
|
Resolution
|
Accuracy
|
|
0.0...999.9 kΩ
|
0.1 kΩ
|
± (3% m.v. + 20 digits)
|
|
1.000...9.999 MΩ
|
0.001 MΩ
|
|
10.00...99.99 MΩ
|
0.01 MΩ
|
|
100.0…999.9 MΩ
|
0.1 MΩ
|
|
1.000...9.999 GΩ
|
0.001 GΩ
|
|
10.00...99.99 GΩ
|
0.01 GΩ
|
|
100.0...999.9 GΩ
|
0.1 GΩ
|
|
1.000...5.000 TΩ
|
0.001 TΩ
|
± (4% m.v. + 50 digits)
|
|
RampTest insulation resistance measurement
|
|
Range
|
Resolution
|
Accuracy
|
|
0.0...999.9 kΩ
|
0.1 kΩ
|
±(5% m.v. + 40 digits)
|
|
1.000...9.999 MΩ
|
0.001 MΩ
|
|
10.00...99.99 MΩ
|
0.01 MΩ
|
|
100.0…999.9 MΩ
|
0.1 MΩ
|
|
1.000...9.999 GΩ
|
0.001 GΩ
|
|
10.00...99.99 GΩ
|
0.01 GΩ
|
|
100.0...999.9 GΩ
|
0.1 GΩ
|
|
1.000...4.999 TΩ
|
0.001 TΩ
|
|
DC and AC voltage measurement
|
|
Range
|
Resolution
|
Accuracy
|
|
0...299.9 V
|
0.1 V
|
±(3% m.v. + 2 digits)
|
|
300...750 V
|
1 V
|
|
Technical specification
|
|
Type of insulation
|
double
|
|
Measurement category
|
CAT III 600 V (CAT IV 300 V)
|
|
Degree of housing protection
|
IP65
|
|
Power supply of the meter
|
SONEL battery pack NiMH 9.6 V 2 Ah
|
|
Battery charging time
|
usually 4 h, max. 10 h
|
|
Parameters of the external power supply adapter
|
90 V…264 V, 50 Hz…60 Hz
|
|
Dimensions
|
200 x 150 x 75 mm
|
|
Meter weight
|
approx. 1.0 kg
|
|
Operating temperature
|
-15…+40°C
|
|
Display
|
modular LCD
|
|
Memory of measurement results
|
990 cells
|
|
Data transmission
|
USB
|
Standard accessories:
- MIC-5001
- Shielded test lead with banana plugs; 5 kV; 1.8 m; black
- Test lead with banana plugs; 5 kV; 1.8 m; red
- Test lead with banana plugs; 5 kV; 1.8 m; blue
- Black “crocodile” clip 11 kV 32 A
- Red “crocodile” clip 11 kV 32 A
- Blue “crocodile” clip 11 kV 32 A
- Test probe with banana socket; 5 kV; black
- Test probe with banana socket; 5 kV; red
- USB cable
- Meter power adapter (type Z7)
- 230 V power cord (IEC C7 plug)
- Sonel Reader PC software
- M-8 carrying case
Optional accessories:
- Test lead 5 m / 10 m, black, 5 kV (banana plugs, shielded)
- Test lead 5 m / 10 m, red, 5 kV (banana plugs, shielded)
- Test lead 5 m / 10 m, blue, 5 kV (banana plugs, shielded)
- Cable for battery charging from car cigarette lighter socket (12 V)
- PRS-1 resistance test probe
- CS-5kV calibration box