Insulation resistance measurement (UN = 15 000 V: 50 kΩ…40.0 TΩ) |
||
|
Range |
Resolution |
Accuracy |
|
0…999 kΩ |
1 kΩ |
±(3% m.v. + 10 digits) |
|
1.00…9.99 MΩ |
0.01 MΩ |
|
|
10.0…99.9 MΩ |
0.1 MΩ |
|
|
100…999 MΩ |
1 MΩ |
|
|
1.00…9.99 GΩ |
0.01 GΩ |
|
|
10…0…99.9 GΩ |
0.1 GΩ |
|
|
100…999 GΩ |
1 GΩ |
±(3.5% m.v. + 10 digits) |
|
1.00…9.99 TΩ |
0.01 TΩ |
±(7.5% m.v. + 10 digits) |
|
10.0…20.0 TΩ |
0.1 TΩ |
±(12.5% m.v. + 10 digits) |
|
10.0…40.0 TΩ |
||
|
Capacitance measurement |
||
|
Range |
Resolution |
Accuracy |
|
0…999 nF |
1 nF |
±(5% m.v. + 5 digits) |
|
1.00…49.99 μF |
0.01 μF |
|
|
Technical specification |
||
|
Type of insulation |
double |
|
|
Measurement category |
IV 1000 V (operating altitude ≤2000 m) |
|
|
Ingress protection |
IP67 (IP40 for closed case) |
|
|
Resistance to external interference voltages |
up to 1550 V |
|
|
Resistance to external interference currents |
up to 10 mA |
|
|
Advanced, digital filtering of interferences |
10 / 30 / 60 / 100 / 200 seconds |
|
|
Test leads lock |
yes |
|
|
Power supply |
Li-Ion 14.8 V rechargeable battery |
|
|
Dimensions |
390 x 308 x 172 mm |
|
|
Weight |
approx. 6.3 kg |
|
|
Storage temperature |
-25ºC…+70ºC |
|
|
Operating temperature |
-20ºC…+50ºC |
|
|
Humidity |
20%…90% |
|
|
Operating altitude |
≤3000 m |
|
|
Reference temperature |
+23ºC ± 2ºC |
|
|
Reference humidity |
40%…60% |
|
|
Display |
graphical LCD |
|
|
Number of Riso measurements with battery power supply |
min. 1000 |
|
|
Data transmission |
USB and Bluetooth |
|