Logo_ESKAN.png
UA EN

MPI-530 Multifunction electrical instalations meter

The MPI-530 is a multifunctional measuring device used for acceptance and interval testing of electrical installations. It combines the functionality of the MZC, MRP, MIC, TKF and MRU series. The extended standard equipment includes everything you need for quality work in accordance with regulatory documentation.

Manufacturer: SONEL S.A. (Poland).

Features
  • Measurement of short circuit loop impedance with resolution 0,001 Ω and 23 A current
  • Measurement of short circuit loop impedance with resolution 0,01 Ω, in protected systems without tripping the RCD’s with I > 30 mA
  • Tests of residual current devices (RCD), types AC, A and B
  • Automatic measurement of all RCD parameters (when the START button is pressed, the meter performs the whole measurement cycle, including the L-PE short circuit loop impedance measurement with 15 mA current)
  • Insulation resistance measurements test voltage values: 50 V, 100 V, 250 V, 500 V and 1000 V
  • Insulation resistance measurements up to 10 GΩ
  • In-socket measurements using the UNI-Schuko adapter
  • Low-voltage resistance measurement of equipotential and protective bonding
  • Earth resistance measurements
  • Soil resistivity measurements
  • Illuminance measurements
  • Quick check of PE connection correctness
  • Measurement and recording of voltage, frequency, AC, cosφ and power (active,reactive and apparent), voltage and current harmonics up to 40, THD
  • Checking reactive phase sequence and motor direction of rotation
  • Power supply from rechargeable of disposable batteries (optional)
  • The meter conforms to EN 61557

Short circuit loop impedance measurement ZL-PE, ZL-N, ZL-L

Range

Resolution

Accuracy

0,000...19,999 Ω

0,001 Ω

± (5% m.v. + 30 digits)

20,00...199,99 Ω

0,01 Ω

200,0...1999,9 Ω

0,1 Ω

Short-circuit loop impedance measurement ZL-PE

Range

Resolution

Accuracy

0,00...19,99 Ω

0,01 Ω

± (6% m.v. + 10 digits)

20,0...199,9 Ω

0,1 Ω

± (6% m.v. + 5 digits)

200...1999 Ω

1 Ω

Measurement of earth resistance RE with the 3p and 4p method

Range

Resolution

Accuracy

0,00...9,99 Ω

0,01 Ω

± (2% m.v. + 4 digits)

10,0...99,9 Ω

0,1 Ω

± (2% m.v. + 3 digits)

100...999 Ω

1 Ω

1,00...1,99 kΩ

0,01 kΩ

Selective earth resistance measurement with clamp (3p + clamp)

Range

Resolution

Accuracy

0,00...9,99 Ω

0,01 Ω

± (8% m.v. + 4 digits)

10,0...99,9 Ω

0,1 Ω

100...999 Ω

1 Ω

1,00...1,99 kΩ

0,01 kΩ

Selective earth measurement with two clamps

Range

Resolution

Accuracy

0,00...9,99 Ω

0,01 Ω

± (10% m.v. + 4 digits)

10,0...19,9 Ω

0,1 Ω

20,0...99,9 Ω

0,1 Ω

± (20% m.v. + 4 digits)

Soil resistivity mesurement (ρ)

Range

Resolution

Accuracy

0,0...99,9 Ω

0,1 Ω

Depending on accuracy
of RE measurement

100...999 Ω

1 Ω

1,00...9,99 Ω

0,01 kΩ

10,0…99,9 kΩ

0,1 kΩ

Insulation resistance measurement

Range

Resolution

Accuracy

0...1999 kΩ

1 kΩ

± (3% m.v. + 8 digits)

2,00...19,99 MΩ

0,01 MΩ

20,0...199,9 MΩ

0,1 MΩ

200...999 MΩ

1 MΩ

1,00...9,99 GΩ

0,01 GΩ

± (4% m.v. + 6 digits)

Low-voltage measurement of resistance and circuit continuity

Range

Resolution

Accuracy

0,00...19,99 Ω

0,01 Ω

± (2% m.v. + 3 digits)

20,0...199,9 Ω

0,1 Ω

200...400 Ω

1 Ω

Illuminance measurement

Range

Resolution

Accuracy

0,1...99,9 lx

0,1 lx

± (5% m.v. + 2 digits)

100...999 lx

1 lx

1,00...9,99 klx

0,01 klx

10,0...19,9 klx

0,1 klx

Measurement of active power P, reactive power Q, apparent power S and cosϕ

Range
[W], [VA], [var]

Resolution
[W], [VA], [var]

Accuracy

0...999

1k

± (7% m.v. + 3 digits)

1,00...9,99k

0,01k

10,0...99,9k

0,1k

± (7% m.v. + 5 digits)

100...999k

1k

1,00...1,50M

0,01M


Standard accessories:

  • MPI-530
  • Adapter with START button with UNI-Schuko (WS-03)
  • Test lead with banana plug; 1,2m; yellow
  • Test lead with banana plug; 1,2m; blue
  • Test lead with banana plug; 1,2m; red
  • Teast lead on a reel with banana plugs; 15m; blue
  • Test lead on a reel with banana plugs; 30m; red
  • USB cable
  • Pin probe with banana connector; yellow
  • Pin probe with banana connector; red
  • Pin probe with banana connector; blue
  • "Crocodile" clip K02; yellow
  • "Crocodile" clip K02; red
  • "Crocodile" clip K02; blue
  • Earth contact test probe (rod); 0,30m
  • Carrying case L2
  • Set of hanging straps
  • Power supply adaptor Z7
  • Cable for battery charger
  • Cable for battery charge with car plug 12V
  • NiMH 4,8V 4,2Ah rechargeable battery
  • Software „Sonel Reader”

Optional accessories:

  • Adapter WS-04 with UNI-Schuko
  • Adapter AutoISO 1000C
  • Test lead on a reel with banana plugs; 50m
  • Test lead on a reel with banana plugs; 25m; blue
  • Test lead with banana plug 5m; red
  • Test lead with banana plugs; 10m; red
  • Test lead with banana plug 20m; red
  • Current clamp C-3
  • Current clamp C-6
  • Transmitting clamp N1 (with test lead)
  • Flexible clamp F-1, 40cm
  • Flexible clamp F-2, 25cm
  • Flexible clamp F-3, 13cm
  • Triple phase socket adapter AGT-16P
  • Triple phase socket adapter AGT-32P
  • Triple phase socket adapter AGT-63P
  • Triple phase socket adapter AGT-16C
  • Triple phase socket adapter AGT-32C
  • Adapter for industrial sockets AGT-16T
  • Adapter for industrial sockets AGT-32T
  • Light meter probe LP1 with WS-06 plug
  • Box for batteries
  • Mini bluetooth keyboard with casing
  • RCD breaker testing adapter TWR-1J
  • Earth contact test probe (rod); 0,80m
  • Software for creation of documentation from electrical measurements "Sonel Reports"
  • Software „SONEL Schematic”
  • Hardware Adapter for Sonel PE program
Back to the list