Short circuit loop impedance measurement ZL-PE, ZL-N, ZL-L |
||
|
Range |
Resolution |
Accuracy |
|
0,00...19,99 Ω |
0,01 Ω |
± (5% m.v. + 3 digits) |
|
20,0...199,9 Ω |
0,1 Ω |
|
|
200...1999 Ω |
1 Ω |
|
|
Short-circuit loop impedance measurement ZL-PE |
||
|
Range |
Resolution |
Accuracy |
|
0,00...19,99 Ω |
0,01 Ω |
± (2% m.v. + 4 digits) |
|
20,0...199,9 Ω |
0,1 Ω |
± (2% m.v. + 3 digits) |
|
200...1999 Ω |
1 Ω |
|
|
Measurement of earthing RE |
||
|
Range |
Resolution |
Accuracy |
|
0,00...9,99 Ω |
0,01 Ω |
± (2% m.v. + 4 digits) |
|
10,0...99,9 Ω |
0,1 Ω |
± (2% m.v. + 4 digits) |
|
100...999 Ω |
1 Ω |
|
|
1,00...1,99 kΩ |
0,01 kΩ |
|
|
Insulation resistance measurement |
||
|
Range |
Resolution |
Accuracy |
|
0...1999kΩ |
1kΩ |
± (3% m.v. + 8 digits) |
|
2,00...19,99MΩ |
0,01MΩ |
|
|
20,0...199,9MΩ |
0,1MΩ |
|
|
200...999MΩ |
1MΩ |
|
|
1,00...3,00GΩ |
0,01GΩ |
± (4% m.v. + 6 digits) |
|
1,00...9,99GΩ |
0,1GΩ |
|
|
Low voltage test of the circuit and insulation continuity |
||
|
Range |
Resolution |
Accuracy |
|
0,00...19,99 Ω |
0,01 Ω |
± (2% m.v. + 3 digits) |
|
20,0...199,9 Ω |
0,1 Ω |
|
|
200...400 Ω |
1 Ω |
|
|
Other parameters |
||
|
Operation temperature |
0...+50°C |
|
|
Type of insulation |
double, according to EN 61010-1and IEC 61557, EMC |
|
|
Measurement category |
IV 300V acc. to EN 61010-1 |
|
|
Casing protection class acc. to PN-EN 60529 |
IP54 |
|
|
Power supply |
alkaline batteries LR14 (4 pcs.) or battery package Ni-MH |
|