Logo_ESKAN.png
UA EN

PGK 260 HB High-voltage test set

The PGK 260 HB is used to generate continuously adjustable test 260 kV DC voltages with positive or negative polarity and 190 kV AC voltages at mains frequency (optional).

Manufacturer: BAUR (Austria).

Description

The test set consists of an operating unit and an HV unit. The operating unit contains all operating and display elements and allows the HV unit to be controlled from a safe distance. Depending upon the operating mode, a rectifier or resistance rod (option) is used in the HV unit. The polarity of the test DC voltage can be reversed by rotating the rectifier rod in the HV unit.
Features
  • Test voltages up to AC 190 kVrms (optional) or DC ±260 kV
  • Oil-insulated maintenance-free high voltage transformer
  • Continuously adjustable output voltage
  • Safety control unit according to EN 50191
  • Voltmeter with 2 measurement ranges
  • Ammeter with 3 measurement ranges
  • Thermal overcurrent switch-off
  • Robust two-part structure

Testing

Output voltage

DC 0 to ±260 kV
AC 0 –
190 kVrms

Output current (continuous)

DC ±4 mA
AC
9 mArms

Short-circuit current

DC ±20 mA
AC
20 mArms

Accuracy voltmeter (kV) and ammeter (mA)    

2.5%

General

Power supply

200 260 V, 50/60 Hz
100
130 V, 50/60 Hz (optional with external auto transformer)

Power consumption

2.6 kVA (5.0 kVA in short-circuit)

Ambient temperature (operational)

0 to +45 °C

Storage temperature

-20 to +60°C

Relative humidity

non-condensing

Dimensions Operating unit (W x H x D)

approx. 506 x 258 x 319 mm, (19“, 5 RU)

Dimensions HV unit (Height / Diameter)

approx. 2 055 mm / Ø 1 265 mm

Weight Operating unit

approx. 19 kg

Weight HV unit

approx. 280 kg

Standard accessories:

  • PGK 260 HB
  • GDR 260-1750 discharge and earth rod
  • Connection cable, 5 m, for connecting the HV unit to the operating unit
  • HV connection cable, 2.5 m, with connection clip
  • Rectifier rod for DC voltage operation, screwed into the HV unit
  • Wrench for changing the rectifier and resistance rod
  • Earth cable, 3 m, with earth terminal
  • Mains supply cord, 2.5 m
  • User manual

Optional accessories:

  • GDR 260-1750 discharge and earth rod
  • Trolley for HV part
  • Hinged stand for 19” devices, height 5 RU (222 mm)
  • EM 260 automatic discharge unit; 90 kJ
  • Transport case for operating and HV unit (Dimensions (W x H x D) approx. 1,350 x 2,220 x 1,350 mm)
  • External emergency off unit with signal lamps, incl. connection cable, 25 m, on hand drum
  • External emergency off unit with signal lamps, incl. connection cable, 50 m, on hand drum
  • External auto transformer 110/230 V; 3.0 kVA
  • Resistance rod for AC voltage operation
  • Rectifier rod