Logo_ESKAN.png
UA EN

PGK 150/5 HB High-voltage test set

The PGK 150/5 HB is used to generate continuously adjustable test 150 kV DC voltages with positive or negative polarity and 110 kV AC voltages at mains frequency.

Manufacturer: BAUR (Austria).

Description

The test set consists of an operating unit and an HV unit. The operating unit contains all operating and display elements and allows the HV unit to be controlled from a safe distance. Depending upon the operating mode, a rectifier or resistance rod is used in the HV unit. The polarity of the test DC voltage can be reversed by rotating the rectifier rod in the HV unit.
Features
  • Test voltages up to AC 110 kVrms or DC ±150 kV
  • Oil-insulated maintenance-free high voltage transformer
  • Continuously adjustable output voltage
  • Safety control unit according to EN 50191
  • Voltmeter with 2 display ranges
  • Ammeter with 3 display ranges
  • Thermal overcurrent switch-off
  • Robust two-part structure

Testing

Output voltage

AC 0 – 110 kVrms
DC 0 to ±150 kV

Output current (continuous)

AC 50 mArms
DC ±18 mA

Short-circuit current

AC 108 mArms
DC ±77 mA

Accuracy voltmeter (kV) and ammeter (mA)    

2.5%

General

Power supply

200 260 V, 50/60 Hz
100
130 V, 50/60 Hz (optional with external auto transformer)

Power consumption

5.75 kVA (11.7 kVA in short-circuit)

Ambient temperature (operational)

0 to +45 °C

Storage temperature

-20 to +60°C

Relative humidity

non-condensing

Dimensions Operating unit (W x H x D)

approx. 506 x 572 x 390 mm, (19“, 12 RU)

Dimensions HV unit (Height / Diameter)

approx. 1,530 mm / Ø 640 mm

Weight Operating unit

approx. 51 kg

Weight HV unit

approx. 180 kg


Standard accessories:

  • PGK 150/5 HB
  • GDR 160-1000 discharge and earth rod
  • Connection cable, 5 m, for connecting the HV unit to the operating unit
  • HV connection cable, 2.5 m, with connecting clip
  • Rectifier rod for DC voltage operation, screwed into the HV unit
  • Resistance rod for AC voltage operation
  • Wrench for changing the rectifier and resistance rod
  • Earth cable, 3 m, with earth terminal
  • Mains supply cord, 2.5 m
  • User manual

Optional accessories:

  • GDR 160-1000 discharge and earth rod
  • Trolley for HV unit
  • Hinged stand for 19” devices, height 12 RU (553 mm)
  • EM 150 automatic discharge unit; 45 kJ
  • Transport case for operating unit (Dimensions (W x H x D) approx. 596 x 616 x 596 mm)
  • Transport case for HV unit (Dimensions (W x H x D) approx. 730 x 1,745 x 730 mm)
  • External emergency off unit with signal lamps, incl. connection cable, 25 m, on hand drum
  • External emergency off unit with signal lamps, incl. connection cable, 50 m, on hand drum
  • External auto transformer 110/230 V, 6.0 kVA
  • Rectifier rod
  • Resistance rod
Back to the list