Logo_ESKAN.png
UA EN

PHG 70 portable | PHG 80 portable VLF test system

The PHG 70 portable | PHG 80 portable are used for cable and cable sheath testing of medium-voltage cables of up to 50 kV and electrical equipment.

Manufactory: BAUR (Austria).

Features
  • VLF truesinus® up to 38 / 57 kVrms
  • VLF square wave up to 57 / 80 kV
  • DC voltage up to ±70 / ±80 kV
  • Cable testing according to: IEC 60502, DIN VDE 0276-620/621 (CENELEC HD 620/621), IEC 60060.3, IEEE 400.2-2013, IEEE 400-2012
  • Cable sheath testing according to IEC 60229
  • Testing of generators, transformers and switchgear
  • High performance test generator (3 kW) with adjustable output voltage
  • Compact, in a 19” housing
  • Control via laptop
  • Load-independent, reproducible sinusoidal high voltage by means of VLF truesinus® technology
  • Adjustable test frequency: 0,01 Hz – 1 Hz
  • Individually programmable, fully automatic test sequences
  • Greater flexibility via “Manual test” mode
  • Automatic breakdown detection
  • Burn mode or safe shutdown on breakdown
  • Control of test generator with professional, self-explanatory software in 23 languages
  • Cable database for management of cable data and structured, easy to search storage of logs
  • Safety control unit in compliance with EN 50191
  • Reverse voltage protection 50 Hz – 16 kV
  • Variable connection options to cable stations of different models
  • Standalone system or for installation in cable test vans

Output voltage

PHG 70 portable

PHG 80 portable

Frequency range

0.01 – 1 Hz

0.01 – 1 Hz

VLF truesinus®

1 – 38 kVrms
1.4 – 53.7 kVpeak

1 – 57 kVrms
1.4 – 80.6 kVpeak

VLF square wave voltage

1 – 57 kV

1 – 80 kV

DC voltage

0 to ±70 kV

0 to ±80 kV

Max. capacitive load

up to 20 μF

3 μF @ 0.1 Hz @ 38 kV
rms
4 μF @ 0.1 Hz @ 30 kVrms

up to 20 μF
1.2 μF @ 0.1 Hz @ 57 kV
rms
3 μF @ 0.1 Hz @ 38 kV
rms
4 μF @ 0.1 Hz @ 30 kVrms

Resolution

0.1 kV

0.1 kV

Accuracy

1%

1%

Output current

PHG 70 portable

PHG 80 portable

Measurement range

0 – 200 mA

0 – 200 mA

Output current

10 mA @ 70 kV
60 mA @ 50 kV
90 mA @ 20 kV

1.8 mA @ 80 kV

60 mA @ 50 kV
90 mA @ 20 kV

Max. burn current

120 mA

120 mA

Resolution

10 μA

10 μA

Accuracy

1%

1%

Laptop

Processor

Intel Core i5

Operating system

Windows 7 Ultimate 32-bit (or higher)

Working memory

At least 4 GB

Hard disk

At least 256 GB SSD

General

Power supply

200 260 V, 50/60 Hz

Option

100 – 140 V, 50/60 Hz (with auto transformer)

Max. power consumption

3 500 VA

Degree of protection

IP22

Dimensions HV generator (W x H x D)      

approx. 755 x 850 x 991 mm (19", 15 RU)

Weight HV generator

approx. 199 kg, incl. rack and connection cable

Ambient temperature (HV generator)

-20 to +55°C

Storage temperature (HV generator)

-30 to +70°C

Relative humidity

non-condensing

Safety and EMC

CE-compliant in accordance with
Low Voltage Di­rective (2014/35/EU),
EMC Directive (2014/30/ EU),
EN 60068-2-ff Environmental testing

Software available in 23 languages

English, Arabic, Chinese (CN), Chinese (TW), Czech, Danish,
Dutch, German, Finnish, French, Greek, Italian, Korean, Malay,
Norwegian, Polish, Portuguese, Romanian, Russian, Serbian,
Swedish, Spanish, Turkish


Standard accessories:

  • PHG 70 portable | PHG 80 portable
  • PHG 70 or PHG 80 HV generator
  • SCU safety control unit
  • Laptop with pre-installed Windows 7 Ultimate, BAUR system software and MS Office, incl. carrying bag
  • GDR 80-500 discharge and earth rod
  • 19” rack for PHG 70/80 portable incl. HV connection cable, earth cable and mains supply cord, cable lengths of 10 m respectively
  • Set of 4 wheels for 19” rack, mounted
  • Carry handles for 19” rack
  • User manual

Optional accessories:

  • External auto transformer, 110/230 V; 3.0 kVA
  • BAUR PD-TaD 80 portable PD diagnostics system
Back to the list