Logo_ESKAN.png
UA EN

tracy Partial discharge inductor

The tracy partial discharge inductor is used for the exact location of partial discharge positions in cables and cable accessories (partial discharge pin-pointing).

Manufactory: BAUR (Austria).

Description

tracy induces a signal at the pre-located partial discharge position in the cable that can be recorded with a partial discharge diagnostics and location system, e.g. PHG 70/80 TD PD or PD-TaD. This allows the operator to compare the location at which the signal is fed in with the pre-located fault location and precisely locate the partial discharge position.

Features
  • Exact location of the partial discharge positions in the exposed cable segment
  • Inductive signal input without damaging the cable
  • Output current adjustable in 9 steps
  • Allows the operator to confirm the fault location pre-located with a PD diagnostics and location system
  • Easy to operate
  • Robust, splash-proof housing
  • Lightweight

General

Output current

Adjustable in 9 steps:

4.0 A
4.6 A
5.0 A

5.6 A
6.0 A
6.4 A

7.0 A
7.3 A
7.7 A

Pulse width

Approx. 25 ns

Pulse rate

20 ms – 5.1 s (in steps of 20 ms)

Integrated battery

NiMH Mignon AA 2,700 mAh

Ambient temperature (operational)        

-10°C to +50°C

Storage temperature

-20°C to +60°C

Relative humidity

Non-condensing

Dimensions (W x H x D)

Approx. 110 x 213 x 42 mm

Weight

Approx. 0.55 kg

Degree of protection

IP54

Safety and EMC

CE compliant in accordance with
Low Voltage Directive (2014/35/EU),
EMC Directive (2014/30/EU),
EN 60068-2-ff Environmental testing      

NiMH Mignon battery

Battery type

NiMH Mignon AA 2,700 mAh

Battery life

Approx. 20 h

Charging time

Approx. 4 h

Charger
   Power supply
   Output voltage


90 – 264 V, 50/60 Hz
DC 4.8 – 12 V, 800 A


Standard accessories:

  • tracy
  • Charger incl. country-specific adapter (UK, Europe, USA, Australia)
  • Induction cable, blue
  • Transport case
  • User manual

Optional accessories: